Water treatment for Hydronic System is performed by injecting chemical scale and corrosion inhibitors through a Chemical Pot Feeder.
The capacity of the Chemical Pot Feeder depends on the water volume in the Hydronic system as follows:
System Water Volume
|
Feeder Size gal
|
Up to 1000
|
5
|
1000 - 10000
|
12
|
Over 10000
|
18
|
Note that oversizing the Chemical Pot Feeder causes more oxygen in the water because of larger air space within the chemical tank.